ALSECURE Z1G-YMz1Kas B2ca Flex 4x150 mm2

Description

Description

Standards

  • Product
    HD 604 S1 part 5/sect. C; IEC 60228

Applications

Nexans Z1G-YMz1Kas B2ca is an armoured halogen free power cable according to fire classification B2ca-s1,d1,a1 for use in low voltage installations up to 0.6/1 kV in buildings and civil engineering works with a very high fire hazard level (NEN 8012). Nexans Z1G-YMz1Kas B2ca is suitable for direct burial and is advised if protection against mechanical damage and EMI is demanded. This cable has reduced propagation of fire in cable bundles.

Main benefits

PEP EcoPassport - EPD environmental passport available
UV Resistant - Our cables passed the 720 hour test according to the test standard EN 50289-4-17 Method A

Design

  1. Conductor: Bare copper, stranded, class 2
     
  2. Insulation: XLPE
     
  3. Inner covering: Halogen free compound or foil for sector shaped types
     
  4. Armour: Galvanized steel wires and bare copper wire or Flat steel wires and flat bare copper wires covered with an open counter spiral of galvanized steels tape 
     
  5. Outer sheath: Halogen free compound
    Colour: grey
    UV resistance: Yes

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2
Conductor shape
Sector-shaped stranded (SM)
Conductor material
Bare copper
Insulation
XLPE (Cross-linked Polyethylene)
Core identification
Blue, brown, black, grey
Inner sheath
special halogen free material, easy to strip
Armour type
Flat steel wires and flat bare copper wires covered with an open counter spiral of galvanized steel tape
Outer sheath
Halogen free compound
Sheath colour
Grey
Halogen free
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
4
Conductor cross-section
150 mm²
Cross-section of the protection cores
75 mm²
Approximate weight
7653 kg/km
Nominal outer diameter
48.9 mm
Nominal insulation thickness
1.4 mm
Inner sheath thickness
1.1 mm
Diameter over filler / inner sheath
41.3 mm
Armour thickness
1.4 mm
Nominal outer sheath thickness
2.5 mm

Electrical characteristics

Electrical characteristics

DC permissible current rating
271 A
Loop resistance, max. at 20°C
0.25 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Excellent

Usage characteristics

Usage characteristics

Bending factor when laying
14 (xD)
One single bending at each end minimum
8 (xD)
Field of application
Fixed installations
Minimum installation temperature
5 °C
Operating temperature, range
-20 ... 80 °C
Max. conductor temperature in service
90 °C
U.V resistance
EN 50289-4-17 method A, for 720h

Resources

Resources

Current capacity table PR three phase single core

Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu
150.0 285.0 342.0 371.0 251.0 287.0 444.0 464.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
D1 Single or Multi-core cable in ducts in the ground
C Single-core or multi-core cable on a wooden wall
D2 Single or Multi-core cables designed to be buried directly in the ground
F Single-core trefoil cables, touching in free air
F Single-core flat cables, touching in free air

Current capacity table PR single phase multicore

Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu
150.0 290.0 334.0 441.0 306.0 343.0 473.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Multi-core cable in ducts in the ground
D2 Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table PR single phase single core

Conductor cross-section
mm² Cu Cu Cu Cu
150.0 318.0 393.0 441.0 504.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
F Single-core flat cables, touching in free air

Current capacity table PR three phase multicore NL

Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu
150.0 259.0 300.0 371.0 251.0 287.0 399.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
D1 Multi-core cable in ducts in the ground
C Single-core or multi-core cable on a wooden wall
D2 Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Selling & delivery Information

Marking

ALSECURE® Z1G-YMz1Kas B2ca
n x s
NEXANS BENELUX
KEMA KEUR
+Meter Marking

Declaration of Performance

  • Declaration of Performance n� : 1000784-BEDO
  • Certification Date : 12/1/23
  • AVCP (Assessment and Verification of Constancy of Performance) : System 1+
  • Notified body : NB 2658
  • Declared performance : B2ca-s1a,d1,a1

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close