ALSECURE YMz1K Cca Easy Strippable 5G6 (B500)

Description

Description

Standards

  • Product
    HD 604 S1 part 5/sect. C; IEC 60228

Applications

ALSECURE YMz1K Cca is a halogen free low smoke power cable for general use in construction works subject to performance requirements on reaction to fire.
ALSECURE YMz1K Cca  is suitable for application in low voltage installations up to 0.6/1 kV, according to NEN 1010. It meets the requirements according to fire classification Cca-s1,d1,a1 for buildings and civil engineering works with a high fire hazard level (NEN 8012).
Available from 35 mm2: ALSECURE YMz1K Cca FLEX, provided with conductors with increased bendability.

Design

  1. Conductor
    Sections till 10 mm2: Bare copper, solid , class 1
    Sections from 10 mm2:  Bare copper, stranded, class 2
  2. Insulation: XLPE
  3. Inner covering: Halogen free compound
  4. Outer sheath: Halogen free compound
    Colour: grey
    UV resistance: Yes

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Solid class 1
Insulation
XLPE (Cross-linked Polyethylene)
Core identification
Blue, brown, black, grey, green / yellow
Conductor material
Bare copper
Outer sheath
Halogen free compound
Sheath colour
Grey
Halogen free
Yes
Conductor shape
Round solid
With Green/Yellow core
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
5
Conductor cross-section
6 mm²
Nominal outer diameter
17.2 mm
Approximate weight
555 kg/km
Average insulation thickness
0.7 mm
Nominal outer sheath thickness
1.8 mm

Electrical characteristics

Electrical characteristics

Permissible current rating in open air
54 A
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Bending factor when laying
10 (xD)
One single bending at each end minimum
8 (xD)
Field of application
Standard
Minimum installation temperature
0 °C
Operating temperature, range
-20 ... 80 °C
Max. conductor temperature in service
90 °C
U.V resistance
EN 50289-4-17 method A, for 720h

Resources

Resources

Selling & delivery Information

Marking

ALSECURE YMz1K Cca n (x or G) s mm²
NEXANS BENELUX
KEMA KEUR
Meter Marking

 

 

Core identification

 

  • 1 core: neutral
  • 2 cores: brown - light blue
  • 3G cores: green/yellow - light blue - brown
  • 3x cores: black -grey- brown
  • 4 cores: green/yellow - brown-black-grey
  • 5 cores: green/yellow - light blue - brown - black - grey

 

Declaration of Performance

  • Declaration of Performance n� : 1000349-BEBU
  • Certification Date : 12/1/23
  • AVCP (Assessment and Verification of Constancy of Performance) : System 1+
  • Notified body : NB 2658
  • Declared performance : Cca-s1,d1,a1

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.