Nexans Z1O-YMz1Kas B2ca 0.6/1 kV 6x1.5/1.5 mm2 MTR

Description

Description

Standards

  • Product
    HD 604 S1 part 5/sect. C; IEC 60228

Applications

Nexans Z1O-YMz1Kas B2ca 0.6/1 kV is a braided power cable according to fire classification B2ca-s1,d1,a1 for usage in low voltage installations up to 0.6/1 kV in buildings and civil engineering works with a very high fire hazard level (NEN 8012).  Z1O-YMz1Kas B2ca 0.6/1 kV is suitable for direct burial and is advised if protection against mechanical damage and EMI is demanded.

Main benefits

PEP EcoPassport - EPD environmental passport available
UV Resistant - Our cables passed the 720 hour test according to the test standard EN 50289-4-17 Method A

Design

  1. Conductor: Bare copper, solid, class 1
  2. Insulation: XLPE
  3. Inner covering: Halogen free compound
  4. Armour: Galvanized steel wire braiding with an underlaying drainwire of tinned copper
  5. Outer sheath: Halogen free compound
    Colour: grey
    UV resistance: Yes

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Bare copper
Conductor flexibility
Solid class 1
Insulation
XLPE (Cross-linked Polyethylene)
Core identification
Black cores with white numbers
Armour type
Galvanized steel wire braiding
Sheath colour
Grey
Halogen free
Yes
Inner sheath
special halogen free material, easy to strip
Outer sheath
Halogen free compound
With Green/Yellow core
No

Dimensional characteristics

Dimensional characteristics

Number of cores
6
Conductor cross-section
1.5 mm²
Nominal outer diameter
16.3 mm
Approximate weight
426 kg/km
Average insulation thickness
0.7 mm
Inner sheath thickness
0.8 mm
Diameter over filler / inner sheath
- mm
Armour thickness
0.3 mm
Cross-section of the protection cores
1.5 mm²
Nominal outer sheath thickness
1.8 mm
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

DC permissible current rating
- A
Loop resistance, max. at 20°C
12.1 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Excellent

Usage characteristics

Usage characteristics

Bending factor when laying
10 (xD)
One single bending at each end minimum
8 (xD)
Fire retardant
IEC 60332-3
Minimum installation temperature
0 °C
Operating temperature, range
-20 ... 80 °C
Electro magnetic interference resistance
No
Max. conductor temperature in service
90 °C
Field of application
Fixed installations
U.V resistance
EN 50289-4-17 method A, for 720h

Resources

Resources

Selling & delivery Information

Marking

ALSECURE Z1O-YMz1Kas B2ca-s1,d1,a1 n x s
NEXANS BENELUX
KEMA KEUR +
Meter Marking

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close