VG-YMvKas Dca-s2 0.6/1kV 2x10 mm2

Description

Description

Standards

  • Product
    HD 604.4D; IEC 60228
  • Test
    KEMA 42 C-1-4-D

Applications

VG-YMvKas Dca is an armoured power cable according to fire classification Dca-s2,d2,a3 for usage in low voltage installations up to 0.6/1 kV in housing, residential and simular installations with a medium fire hazard level. VG-YMvKas Dca is suitable for direct burial and is advised if protection against mechanical damage and EMI is demanded.  This cable has a reduced propagation of fire in cable bunches.

Available from 35 mm2: VG-YMvKas Dca Flex, provided with conductors having increased bendability.

Design

  1. Conductor
    Bare copper, stranded, class 2
    Insulation: XLPE
  2. Inner covering
    PVC with filler extruded or PET foil for more 5 cond and sector shaped types
  3. Armour
    Galvanized steel wires and bare copper wire or Flat steel wires and flat bare copper wires covered with an open counter spiral of galvanized steel tape
  4. Outer sheath
    PVC
    Colour: grey
    UV resistance: Yes

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2
Conductor shape
Round, stranded
Conductor material
Bare copper
Insulation
XLPE (chemical)
Core identification
Blue, brown
Inner sheath
Extruded inner covering
Armour type
Galvanized steel wires
Outer sheath
PVC
Sheath colour
Grey
Lead free
Yes
With Green/Yellow core
No

Dimensional characteristics

Dimensional characteristics

Number of cores
2
Conductor cross-section
10 mm²
Nominal outer diameter
21.8 mm
Approximate weight
994 kg/km
Cross-section of the protection cores
10 mm²
Average insulation thickness
0.7 mm
Inner sheath thickness
0.8 mm
Armour thickness
1.2 mm
Nominal outer sheath thickness
1.8 mm

Electrical characteristics

Electrical characteristics

DC permissible current rating
77 A
Loop resistance, max. at 20°C
1.83 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Excellent

Usage characteristics

Usage characteristics

Bending factor when laying
16 (xD)
One single bending at each end minimum
8 (xD)
Minimum installation temperature
0 °C
Operating temperature, range
-20 ... 80 °C
Max. conductor temperature in service
90 °C
Electro magnetic interference resistance
Yes
U.V resistance
EN 50289-4-17 method A, for 720h

Resources

Resources

Current capacity table PR single phase multicore

Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu
10.0 57.0 69.0 80.0 71.0 77.0 86.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Multi-core cable in ducts in the ground
D2 Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table PR single phase single core

Conductor cross-section
mm² Cu Cu Cu Cu
10.0 61.0 75.0 80.0 0.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
F Single-core flat cables, touching in free air

Current capacity table PR three phase multicore NL

Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu
10.0 51.0 60.0 71.0 58.0 65.0 75.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
D1 Multi-core cable in ducts in the ground
C Single-core or multi-core cable on a wooden wall
D2 Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table PR three phase single core

Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu
10.0 54.0 66.0 71.0 58.0 65.0 0.0 0.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
D1 Single or Multi-core cable in ducts in the ground
C Single-core or multi-core cable on a wooden wall
D2 Single or Multi-core cables designed to be buried directly in the ground
F Single-core trefoil cables, touching in free air
F Single-core flat cables, touching in free air

Selling & delivery Information

Marking

VG-YMvKas Dca
n x s
NEXANS BENELUX
KEMA KEUR
Meter Marking

 

Declaration of Performance

  • Declaration of Performance n� : 1000905-BEDO
  • Certification Date : 12/1/23
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : NB 2659
  • Declared performance : Dca-s2,d2,a3

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close