Nexans Z1G-YMz1Kas Cca FLEX 0,6/1 kV 3x 70/35 mm2 MTR

Description

Description

Standards

  • Product
    HD 604 S1 part 5/sect. C; IEC 60228

Applications

ALSECURE Z1G-YMz1Kas Cca FLEX is an armoured halogen free power cable according to fire classification Cca-s1,d1,a1 for use in low voltage installation up to 0.6/1 kV in buildings and civil engineering works with a high fire hazard level (NEN 8012).  ALSECURE Z1G-YMz1Kas Cca FLEX is suitable for direct burial and is advised if protection against mechanical damage and EMI is demanded.

Design

  1. Conductor: Bare copper, stranded, class 2
  2. Insulation: XLPE
  3. Inner covering: Halogen free compound or foil for sector shaped types
  4. Armour: Galvanized steel wires and bare copper wire or Flat steel wires and flat bare copper wires covered with an open counter spiral of galvanized steels tape
  5. Outer sheath: Halogen free compound with reduced fire propagation
    Colour: grey
    UV resistance: Yes

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2
Conductor material
Bare copper
Insulation
XLPE (Cross-linked Polyethylene)
Core identification
Brown, black, grey
Inner sheath
special halogen free material, easy to strip
Armour type
Galvanized steel wires
Outer sheath
Halogen free compound
Sheath colour
Grey
Halogen free
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
3
Conductor cross-section
70 mm²
Cross-section of the protection cores
35 mm²
Approximate weight
3111 kg/km
Nominal outer diameter
33.0 mm
Nominal insulation thickness
1.1 mm
Inner sheath thickness
0.9 mm
Diameter over filler / inner sheath
25.7 mm
Armour thickness
1 mm
Nominal outer sheath thickness
2.0 mm

Electrical characteristics

Electrical characteristics

DC permissible current rating
178 A
Loop resistance, max. at 20°C
0.52 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Excellent

Usage characteristics

Usage characteristics

Bending factor when laying
14 (xD)
One single bending at each end minimum
8 (xD)
Field of application
Fixed installations
Minimum installation temperature
5 °C
Operating temperature, range
-20 ... 80 °C
Max. conductor temperature in service
90 °C
U.V resistance
EN 50289-4-17 method A, for 720h

Resources

Resources

Selling & delivery Information

Marking

ALSECURE Z1G-YMz1Kas Cca FLEX
n x s
NEXANS BENELUX
KEMA KEUR
+Meter Marking

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close