YR Dca-s2 2X0,8 mm grey MOBIWAY-500m
YR Dca-s2 2X0,8 mm grey MOBIWAY-500m
YR Dca is a signal cable according to fire classification Dca-s2,d2,a3 for usage in low voltage installations with a medium fire hazard level. Packaging: Mobiway-500m drum.
Read more- Nexans ref. : 10570251
- EAN : 5413404328147
Description
Description
Standards
-
TestIEC 60332-1
Application
Nexans YR Dca-s2 is a signal cable according to fire classification Dca-s2,d2,a3 for usage in signal applications in low voltage installations with a medium fire hazard level.
Description
- Conductor: Solid plain copper conductor, 0.8 mm
- Insulation: PVC
- Conductors: laid up in concentric layers
- Outher sheath: Fire retardant PVC
Colour: Grey or White
Marking
NEXANS-NL YR Dca N x S mm
(N = no. of conductors, S = section in mm)
Core Identification
according NEN 1597 (see technical data, table A)
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Plain copper
Conductor flexibility
Solid
Insulation
PVC
Outer sheath
Fire-retardant PVC
Sheath colour
Grey
Core identification
Red, Blue
Dimensional characteristics
Dimensional characteristics
Number of cores
2
Conductor diameter
0.8 mm
Nominal outer diameter
4.2 mm
Diameter over insulation
- mm
Approximate weight
24 kg/km
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
38.2 Ohm/km
Ohmical resistance of the insulation
1000 MOhm.km
Breakdown voltage
0.8 kV
Maximum operating voltage
150 V
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Mechanical resistance to impacts
Normal domestic use
Usage characteristics
Usage characteristics
Packaging
MOBIWAY™Refill
Field of application
Indoor
Ambient installation temperature, range
-5 ... 50 °C
Operating temperature, range
-15 ... 70 °C
Bending factor when laying
10 (xD)
Resistance to vibrations
No
Resources
Resources
Selling & delivery Information
Marking: NEXANS-NL YR Dca NxS mm (N=No of conductors, S=section in mm)
Declaration of Performance
- Declaration of Performance n� : 1000935-BEBU
- Certification Date : 12/1/23
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : NB 2659
- Declared performance : Dca-s2,d2,a3
Dealer locator